Omron E5CC Series Temperature Controller
The Omron E5CC is a next-generation digital temperature controller featuring a compact 48 × 48 mm design, fast sampling rate, and intuitive interface. Engineered for precise and flexible control in demanding industrial environments, it supports universal input types, offers PID control with autotuning, and is ideal for both simple and complex temperature regulation needs.
Categories:
Panel ComponentsKey Features
- High-Speed Sampling: 50 ms – Ensures fast, stable response to process changes
- Universal Input Support – Thermocouple, RTD, Voltage (mV), and Current (mA)
- High-Contrast White LCD Display – Easy-to-read PV, SV, and parameter values even in low-light
- Multiple Output Options – Relay, voltage pulse, current, and SSR output
- Advanced PID Control – With Auto-Tuning and Self-Tuning functions
- Multiple Alarms – Up to 3 configurable alarms for enhanced safety
- Easy Parameter Setting – Via front keys, USB, or optional communications (RS-485/Modbus)
- Compact Depth: 60 mm – Saves panel space; ideal for high-density installation
- Global Compliance – CE, UL, and RoHS certified
| Specifications | Details | |
|---|---|---|
| Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
| Operating voltage range | 85% to 110% of rated supply voltage | |
| Power consumption | Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or 1.6 W max. at 24 VDC All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC | |
| Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V,or 0 to 50 mV (The 0 to 50 mV range applies to the E5CC-U only for those manufactured in May 2014 or later.) | |
| Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB-N/THB-N.) | |
| Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
| Control output | Relay output | E5CC/E5CC-B: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) E5CC-U: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) |
| Voltage output (for driving SSR) | Output voltage: 12 VDC ± 20% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
| Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
| Auxiliary output | Number of outputs | E5CC: 3 E5CC-B: 2 E5CC-U: 1 or 2 (depends on model) |
| Output specifications | SPST-NO relay outputs, 250 VAC, Models with 1 output: 3 A (resistive load), E5CC-U models with 2 outputs: 3 A (resistive load), E5CC-B models with 2 outputs: 2 A (resistive load), Models with 3 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) | |
| Event input *1 | Number of inputs | E5CC: 2 or 4 (depends on model) E5CC-B: 2 (depends on model) |
| External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
| Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
| Current flow: Approx. 7 mA per contact | ||
| Transfer output *1 | Number of outputs | 1 (only on models with a transfer output) |
| Output specifications | Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10,000 | |
| Setting method | Digital setting using front panel keys | |
| Remote SP input *1 *2 | Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.) Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.) | |
| Indication method | 11-segment digital display and individual indicators Character height: PV: 15.2 mm, SV: 7.1 mm | |
| Multi SP *3 | Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or serial communications. | |
| Bank switching | None | |
| Other functions | Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, simple programming, moving average of input value, and display brightness setting | |
| Ambient operating temperature | -10 to 55°C (with no condensation or icing), For 3-year warranty: -10 to 50°C with standard mounting (with no condensation or icing) | |
| Ambient operating humidity | 25% to 85% | |
| Storage temperature | -25 to 65°C (with no condensation or icing) | |
| Altitude | 2,000 m max. | |
| Recommended fuse | T2A, 250 VAC, time-lag, low-breaking capacity | |
| Installation environment | Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1) | |
| Specifications | Details | ||
|---|---|---|---|
| Indication accuracy (at the ambient temperature of 23°C) | E5CC/E5CC-B Thermocouple: (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max. E5CC-U Thermocouple: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit Analog input: ±0.2% FS ±1 digit max. | ||
| Transfer output accuracy | ± 0.3% FS max. | ||
| Simple transfer output accuracy | ±0.3% FS max.*2 | ||
| Remote SP Input Type | ± 0.2% FS ± 1 digit max. | ||
| Influence of temperature *3 | Thermocouple input (R, S, B, C/W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *4 Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. Analog input: ±1%FS ±1 digit max. CT input: ±5% FS ±1 digit max. Remote SP input: ±1% FS ±1 digit max. | ||
| Influence of voltage *3 | |||
| Influence of EMS. (at EN 61326-1) | |||
| Input sampling period | 50 ms | ||
| Hysteresis | Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) | ||
| Proportional band (P) | Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) | ||
| Integral time (I) | 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 | ||
| Derivative time (D) | 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 | ||
| Proportional band (P) for cooling | Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) | ||
| Integral time (I) for cooling | 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 | ||
| Derivative time (D) for cooling | 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 | ||
| Control period | 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s) | ||
| Manual reset value | 0.0 to 100.0% (in units of 0.1%) | ||
| Alarm setting range | -1999 to 9999 (decimal point position depends on input type) | ||
| Influence of signal source resistance | Thermocouple: 0.1°C/Ω max. (100 Ωmax.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) | ||
| Insulation resistance | 20 MΩ min. (at 500 VDC) | ||
| Dielectric strength | 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge | ||
| Vibration | Malfunction | 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions | |
| Resistance | 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions | ||
| Shock | Malfunction | 100 m/s2, 3 times each in X, Y, and Z directions | |
| Resistance | 300 m/s2, 3 times each in X, Y, and Z directions | ||
| Weight | E5CC/E5CC-B: Controller: Approx. 120 g, Mounting Adapter: Approx. 10 g E5CC-U: Controller: Approx. 100 g, Mounting Adapter: Approx. 10 g | ||
| Degree of protection | E5CC/E5CC-B: Front panel: IP66, Rear case: IP20, Terminals: IP00 E5CC-U: Front panel: IP50, Rear case: IP20, Terminals: IP00 | ||
| Memory protection | Non-volatile memory (number of writes: 1,000,000 times) | ||
| Setup Tool | E5CC: CX-Thermo version 4.5 or higher E5CC-B: CX-Thermo version 4.65 or higher *7 E5CC-U: CX-Thermo version 4.61 or higher | ||
| Setup Tool port | E5CC/E5CC-B/E5CC-U top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port on the computer. *6 | ||
| Standards | Approved standards | cULus: UL 61010-1/CSA C22.2 No.61010-1 *8, KOSHA (S Mark) certification (Some models only.) *9, Korean wireless regulations (Radio law: KC Mark) (Some models only.) *9, Lloyd's standards *10 | |
| Conformed standards | EN 61010-1 (IEC 61010-1), RCM | ||
| EMC | EMI: EN 61326-1 *11 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326-1 *11 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Voltage Dip/Interrupting Immunity: EN 61000-4-11 | ||
Models with Screw Terminals (E5CC-800 48 × 48 mm)
| Control output 1 | Auxiliary output | Communications | Heater burnout | Event inputs | Power supply voltage | Model |
|---|---|---|---|---|---|---|
| Relay output | Two | - | - | - | 100 to 240 VAC | E5CC-RX2ASM-800 |
| Voltage output | E5CC-QX2ASM-800 | |||||
| Linear current output | E5CC-CX2ASM-800 | |||||
| Relay output | 24 VAC/VDC | E5CC-RX2DSM-800 | ||||
| Voltage output | E5CC-QX2DSM-800 | |||||
| Linear current output | E5CC-CX2DSM-800 | |||||
| Relay output | One | Two | 100 to 240 VAC | E5CC-RX2ASM-801 | ||
| Voltage output | E5CC-QX2ASM-801 | |||||
| Relay output | 24 VAC/VDC | E5CC-RX2DSM-801 | ||||
| Voltage output | E5CC-QX2DSM-801 | |||||
| Relay output | RS-485 | - | 100 to 240 VAC | E5CC-RX2ASM-802 | ||
| Voltage output | E5CC-QX2ASM-802 | |||||
| Relay output | 24 VAC/VDC | E5CC-RX2DSM-802 | ||||
| Voltage output | E5CC-QX2DSM-802 | |||||
| Linear current output | - | Two | 100 to 240 VAC | E5CC-CX2ASM-804 | ||
| Linear current output | 24 VAC/VDC | E5CC-CX2DSM-804 |
Plug-in Models (E5CC-U-800 48 × 48 mm)
| Control output 1 | Auxiliary output |
Commu- nications |
Heater burnout |
Event inputs |
Power supply voltage | Model |
|---|---|---|---|---|---|---|
| Relay output | Two | - | - | - | 100 to 240 VAC | E5CC-RW2AUM-800 |
| Voltage output | E5CC-QX2AUM-800 | |||||
| Relay output | 24 VAC/VDC | E5CC-RW2DUM-800 | ||||
| Voltage output | E5CC-QX2DUM-800 |
|
Catalog Name
|
Catalog Number[size]
|
Last Update
|
|---|---|---|
| E5C, E5C-T Data Sheet | H177-E1-16 [40802KB] |
Dec 01, 2023 |
| E5C Brochure | H220-E1-04 [4605KB] |
Oct 02, 2023 |
| Value Design for Panel Catalog | Y235-E1-07 [5229KB] |
May 19, 2025 |
Applications
- Injection molding and plastic machinery
- Heat treatment and furnace control
- Food & beverage processing equipment
- HVAC and temperature-critical storage systems
- Industrial dryers, ovens, and environmental chambers
Why Choose
- Ultra-fast response and precision PID control
- Highly visible display in compact DIN-size housing
- Flexible I/O and communication options
- Simplified parameter setup with optional USB configurator
- Reliable in demanding environments – from ovens to automation panels